【Prev Products】 | 【Next Products】 |
![]() |
|
![]() ![]() ![]() ![]() ![]() |
1.Max58A and 1500V
2.Available in 2 to 4 Pole, application in the distribution box
3.TUV certificated
4.Working Temperature: Full efficiency between -25 ~ 70
5.5 years guarantee certificate
6.Handy Locking Mechanism while off keeps it safe from Children or Un-Authorized access
7.Operator Independent trigger Ratchet Switching and Knife Edge Self Cleaning Contact Mechanism
Technical parameters |
Model |
FDIS-NHV |
||||
The following CNC according to IEC60947-3,the use of category DC-PV1/ DC-PV2 |
||||||
Main parameters |
||||||
Rated insulation voltage |
Ui |
|
V |
1500 |
||
Rated heating current |
Ithe |
|
A |
32 |
||
Rated impulse withstand voltage |
Uimp |
|
V |
8000 |
||
Rated short-time withstand current(1s) |
Icw |
2,4 |
A |
1000 |
||
2H |
A |
1700 |
||||
Rated short-circuit making capacity |
Icm |
2,4 |
A |
1000 |
||
2H |
A |
1700 |
||||
Rated short-circuit current |
Icc |
|
A |
5000 |
||
Maximum fuse specifications |
gL(gG) |
|
A |
80 |
||
Mechanical life |
|
|
|
10000 |
||
DC poles |
|
|
|
2 or 4 |
||
Distance between contacts (pole-to-pole) |
|
|
mm |
8 |
||
Operating temperature |
|
|
℃ |
-25 ~+70 |
||
Storage temperature |
|
|
℃ |
-40 ~+70 |
||
Class of pollution |
|
|
|
2 |
||
Overvoltage category |
|
|
|
I to III |
||
IP level |
|
|
|
IP20 |